Load and Resistance Factor Design (LRFD)

Strength design in which factored loads must not exceed the nominal strength multiplied by a resistance factor.


LRFD requires ϕRn≥Ru\phi R_n \ge R_u: the nominal strength RnR_n, reduced by a resistance factor ϕ\phi below 1.0, must equal or exceed the required strength RuR_u found from loads multiplied by load factors above 1.0. Each factor reflects the uncertainty in what it multiplies.

The basic gravity combinations are 1.4D1.4D and 1.2D+1.6L1.2D + 1.6L; others add wind, snow and earthquake. Steel design under AISC and concrete design under ACI both use this format, with ϕ=0.90\phi = 0.90 for flexure in both and lower values for brittle or less predictable failures such as concrete shear.

How much of the FE Civil exam is Structural Engineering?

Worked example

A floor beam in an office building spans 30 ft between simple supports, 10 ft from its neighbours. It carries a dead load of 0.80 kip/ft (deck, finishes and self weight) and a live load of 1.20 kip/ft, and the deck braces its compression flange along the whole length. The beam is a W18x46 in A992 steel (Fy=50F_y = 50 ksi, Zx=90.7 in3Z_x = 90.7\ \text{in}^3, Sx=78.8 in3S_x = 78.8\ \text{in}^3). Is it adequate in flexure by LRFD?

A simply supported beam spanning 30 ft between a pin on the left and a roller on the right, carrying a uniform dead load of 0.80 kips per foot and a uniform live load of 1.20 kips per foot over its full length.
StepWorkingResult
Combination 11.4D=1.4(0.80)1.4D = 1.4(0.80)1.12 kip/ft
Combination 21.2D+1.6L=1.2(0.80)+1.6(1.20)1.2D + 1.6L = 1.2(0.80) + 1.6(1.20)2.88 kip/ft (governs)
Required momentMu=wuL2/8=2.88(30)2/8M_u = w_u L^2/8 = 2.88(30)^2/8324.0 kip-ft
Nominal momentMn=FyZx=50(90.7)/12M_n = F_y Z_x = 50(90.7)/12377.9 kip-ft
Design strengthϕMn=0.90(377.9)\phi M_n = 0.90(377.9)340.1 kip-ft

ϕMn=340.1\phi M_n = 340.1 kip-ft ≥Mu=324.0\ge M_u = 324.0 kip-ft, so the W18x46 is adequate. Working backwards, the lightest acceptable section needs Zx≥Mu/(ϕFy)=86.4 in3Z_x \ge M_u/(\phi F_y) = 86.4\ \text{in}^3. Because the flange is braced continuously the beam reaches its full plastic moment, which is why ZxZ_x and not SxS_x is used; the 10 ft spacing to the next beam does not enter the check at all.

The same beam by ASD

Allowable Strength Design keeps loads unfactored and divides the strength by a safety factor instead: Ma=(D+L)L2/8=2.00(30)2/8=225.0M_a = (D + L)L^2/8 = 2.00(30)^2/8 = 225.0 kip-ft against Mn/Ω=377.9/1.67=226.3M_n/\Omega = 377.9/1.67 = 226.3 kip-ft. Both methods accept the beam. They agree closely at a live-to-dead ratio near 3, where AISC calibrated them; LRFD gives lighter members when dead load dominates, because the dead load is known more precisely and carries the smaller factor.

LRFD load combinations

CombinationUsually governs for
1.4D1.4DVery high dead load, little live load
1.2D+1.6L+0.5(Lr or S or R)1.2D + 1.6L + 0.5(L_r \text{ or } S \text{ or } R)Floors: most gravity design
1.2D+1.6(Lr or S or R)+(L or 0.5W)1.2D + 1.6(L_r \text{ or } S \text{ or } R) + (L \text{ or } 0.5W)Roofs under snow or roof live load
1.2D+1.0W+L+0.5(Lr or S or R)1.2D + 1.0W + L + 0.5(L_r \text{ or } S \text{ or } R)Lateral design for wind
0.9D+1.0W0.9D + 1.0WUplift and overturning: dead load resists